TiXo3 temperature converters are aimed at converting signals coming from large panel of input signals:
• Coversion of temperature measurement with RTD100, RTD1000, Ni100, Ni1000 or thermocouple.
• Conversion of linear resistance variation (from level sensors or valves).
• Voltage (mV) and ohmic measurement.
These converters are mainly head mounting product and are certified to be located in explosive atmosphere (see codification

			int(7639)
NULL
		

Made in France. brand GEORGIN, model TiXo3

Fast delivery to Latvia, Estonia and Lithuania. International delivery to Europe, Asia, Africa and other continents available on request
Our warehouse is located in Riga, Latvia.

price by request

Available

Available

Advantages

Official distributor in Latvia

Time-tested American, European and Asian brands of control and measurent instruments

Advantages

Special price list for organisations

We offer a significant discount for trade organisations and manufacturing companies

Advantages

Worldwide shipping on request

We take care of all logistics and customs clearance. Fast delivery to Baltic countries

Advantages

After-sales service and support

Warranty service and repair, expert assistance in the operation of the instruments

Technical specifications of GEORGIN TiXo3

Electrical data

  • Input: Programmable (refer to backside)
  • Output: 4/20 mA
  • Power supply:
    Standard model 10V … 30 Vdc
    ATEX version 10V … 28 Vdc
  • Galvanic isolation: 1500V CA
  • Accuracy: ≤ 0.1% F.S. or ≤ basis accuracy (refer to backside) according to the most important value
  • Load resistance: (Vsupply-10) / 0.0215 Ω
  • Shorted or broken line detection: Configurable 3.5 mA to 21.5 mA (NAMUR NE43)
  • Warm-up time: 5 minutes
  • Response time: < 2 s
  • Drift:
    Voltage supply: ≤ 0.01% of the current in the loop for a variation of 0.1% of Vsupply
    Temperature: ≤ 10% of accuracy / degree
  • Error due to CJC: 1.5x basis accuracy for a cold junction at 0°C to be added
  • Line resistance effect:
    RTD100 2wires* / 3wires** 2.5°C/ Ω
    RTD1000 2wires* / 3wires** 0.25°C/ Ω
    Ni100 2 wires* / 3 wires** 2°C/ Ω
    Ni1000 2 wires* / 3 wires** 0.2°C/ Ω
    * : compensation is configurable / ** : unbalance between wires
  • EMC Immunity < 0.1% F.S.

Mechanical data

  • Housing: Plastic (PBT) Ø = 44 mm H = 21.6 mm
  • Protection: IP 00 on terminals
  • Weight: approx. 40 g
  • Working T°: -40°C to 85°C (non ATEX version)
  • Storage T°: -40°C to 85°C
  • Relative humidity: 5%-95% without condensing
  • Connection: Screw terminals – capture screws
  • Max. wire size: 1x 1.5 mm²

Certifications

  • EMC: EN 61326 & IEC 61000-6-2
  • For ATEX products:
    Intrinsic Safety:
    EN 60079-0 & EN 61241-0
    EN 60079-11 & EN 61241-11
    EN60079-26
    “n” type of protection EN 60079-15
  • Certificate N°:INERIS 08ATEX0004X & 08ATEX3002U
  • ATEX Classification:
    CE 0081 II 1 GD Ex ia IIC
    CE 0081 II 1 GD Ex iaD 20
    CE II 3 G Ex nA II
  • Ambiante working T° T4 : -40°C < ambiante T° < 85°C
    T5 : -40°C < ambiante T° < 65°C
    T6 : -40°C < ambiante T° < 50°C

User Guide and Instruction manual for GEORGIN TiXo3

You can request the necessary certificates, documentation, instructions and user guide for GEORGIN TiXo3 using the special form.

You can buy GEORGIN TiXo3 in Latvia at a favourable price in «OLIL SIA» by leaving a request on the website, by phone +371 672 70580 or by email . GEORGIN TiXo3 price are subject to change depending on exchange rates. We deliver instruments by transport companies in Latvia, Estonia and Lithuania. Worldwide shipping to Europe, Asia, Africa, North and South America available on request.