Instantly detect pressurized gas leaks with this high-precision, omni-direction acoustic detector utilizing Gassonic® ultrasonic technology. Works even when traditional methods of gas detection are unsuitable or dependent on ventilation. The Observer-i UGLD provides an industry-leading detection range (up to 28 m) reducing the number of detectors required.
Made in USA. brand MSA Safety, model OBSERVER i
Fast delivery to Latvia, Estonia and Lithuania. International delivery to Europe, Asia, Africa and other continents available on request
Our warehouse is located in Riga, Latvia.
price by request
Available
Official distributor in Latvia
Time-tested American, European and Asian brands of control and measurent instruments
Special price list for organisations
We offer a significant discount for trade organisations and manufacturing companies
Worldwide shipping on request
We take care of all logistics and customs clearance. Fast delivery to Baltic countries
After-sales service and support
Warranty service and repair, expert assistance in the operation of the instruments
Applications
• Floating Production Storage
and Offloading Vessels (FPSOs)
• Gas Compressor and Metering Stations
• Gas Storage Facilities
• Hydrogen Storage Facilities
• LNG / GTL Trains
• LNG Re-gasification Plants
• Offshore and Onshore Oil and Gas Installations
• Petrochemical Processing Plants
Features | Benefits |
ARTIFICIAL NEURAL NETWORK (ANN) | Improved detection range and background noise rejection prevents false alarms |
SENSSONIC INTEGRATED ACOUSTIC SELF-TEST | Failsafe operation |
ONE-PERSON ACOUSTIC SOUND CHECK WITH TRACEABLE PORTABLE TEST UNIT | High reliability and trouble free maintenance |
HART AND MODBUS | Provides complete status and control capability in the control room |
EVENT LOGGING | Stores fault, sound check, calibration, and alarm event history |
DETECTS GAS LEAKS FROM 2 BAR (29 PSI) PRESSURE | Very small gas leaks can be detected quickly |
Electrical Specifications | |
INPUT POWER | 15–36 VDC, 250 mA max.
24 VDC, 170 mA nominal |
RELAY RATINGS (OPTIONAL) | 8 A @ 250 VAC |
CURRENT OUTPUT (SINK OR SOURCE) | Status Indications:
0 mA: Start up, no power 1 mA: Pulsed acoustic error 3 mA: Unit inhibit Classic Mode: 4–20 mA, 40–120 dB (u) ANN Mode: 4–12 mA, 40–120 dB (u) 16 mA, warning 20 mA, alarm |
EMC/RFI | EMC Directive 2014/30/EU EN 61000-6-2, EN 61000-6-4 |
SERIAL DIGITAL COMMUNICATION | HART, Modbus |
CABLE REQUIREMENTS | Max. cable length between Observer-i and power source @ 24 VDC (20 ohm) 2.08 mm2 (14 AWG) – 1,809 m (5,928 ft) |
Environmental Specifications | |
OPERATING TEMPERATURE RANGE | –40°C to 60°C (–40°F to 140°F) |
OPERATING HUMIDITY RANGE | 10–95% RH, non-condensing |
Mechanical Specifications | |
HOUSING | Stainless Steel AISI 316L |
DIMENSIONS | 203 x 203 x 201 mm (7.99 x 7.99 x 7.91 in) |
WEIGHT | 7.5 kg (16.6 lbs) |
CONDUIT ENTRIES | M20 x 1.5 (additional ¾“ NPT adapter available) |
MOUNTING HOLES | 2 x mounting screws – M8 x 19 max |
INGRESS PROTECTION | IP66 / Type 4X |
STANDARD CONFIGURATION | OBSERVER i-1-1-1-1-1-1 |
Gas Name
|
Carbon Dioxide
Ethylene Hydrogen Sulfide Methane Ethane Helium Hydrogen Propane Propylene |
System Specifications | |
DETECTOR TYPE | Ultrasonic (acoustic) gas leak detector |
BACKGROUND NOISE REJECTION METHOD | Artificial Neural Network (ANN) |
GAS LEAK
RECOGNITION METHOD |
Artificial Neural Network (ANN) |
MIN. ACOUSTIC DET. FREQUENCY
(ANN MODE) |
12 kHz |
MIN. DETECTION
LIMIT |
40 dB (u) |
ACCURACY | ±3 dB |
SELF-TEST | Performed every 15 minutes |
MIN. PRESSURE REQUIREMENT | 2 BAR (29 psi) |
DETECTOR
COVERAGE (REF. METHANE) |
Enhanced Mode (ANN) (@ 0.1 kg/sec):
FQHI setting (59 dB ANN sensitivity level): 17 meters (56 ft.) Default Ultra-high to medium background noise FQLO setting (54 dB ANN sensitivity level): 28 meters (92 ft.) Medium to low background noise Classic Mode (@ 0.1 kg/sec): Ultra-high: 7 meters (23 ft.) w/84 dB T.L. High: 12 meters (39 ft.) w/74 dB T.L. Medium: 18 meters (59 ft.) w/64 dB T.L. Low: 24 meters (79 ft.) w/54 dB T.L. |
RESPONSE TIME | < 1 s (speed of sound) |
APPROVALS CLASSIFICATION | ATEX/IECEx:
II 2 G D Ex db ia IIB+H2 T6 Gb, Ex tb IIIC T85°C Db CSA: Ex d ia IIB+H2 Gb T6, Ex tb IIIC T85°C Db FM/CSA: Class I, Div. 1, 2 Groups B,C,D; Class II, Div. 1, 2 Groups E,F,G; Class III, T5 (Ta = –40°C to +60°C) |
APPROVALS | ATEX, CE, UKEx, CSA, FM, IECEx, Inmetro, SANS
HART 6.0 registered FM certified to IEC 61508 (SIL 3) |
ACCESSORIES | 1701 Test and Calibration Unit |
DEVICE DRIVERS | DDL, DTM available here |
WARRANTY | 2 years |
You can request the necessary certificates, documentation, instructions and user guide for MSA Safety OBSERVER i using the special form.
You can buy MSA Safety OBSERVER i in Latvia at a favourable price in «OLIL SIA» by leaving a request on the website, by phone +371 672 70580 or by email olil@olil.lv. MSA Safety OBSERVER i price are subject to change depending on exchange rates. We deliver instruments by transport companies in Latvia, Estonia and Lithuania. Worldwide shipping to Europe, Asia, Africa, North and South America available on request.
See also: Gas detectors & analysers