MACURCO CX-6-CO/CX-12-CO Carbon Monoxide Fixed Gas Detector

CX-6-CO: Low Voltage (12 to 24 VAC or 12 to 32 VDC)/CX-12-CO: Line Voltage (100-240 VAC)

The CX-6-CO/CX-12-CO detects Carbon Monoxide (CO) in commercial facilities such as parking garages, loading docks, etc. It can be used as a stand-alone detector, controller, and as an analog transducer for use with Macurco control panels and other systems

			int(24447)
NULL
		

Made in USA. brand MACURCO, model CX-6-CO/CX-12-CO

Fast delivery to Latvia, Estonia and Lithuania. International delivery to Europe, Asia, Africa and other continents available on request
Our warehouse is located in Riga, Latvia.

price by request

Available

Available

Advantages

Official distributor in Latvia

Time-tested American, European and Asian brands of control and measurent instruments

Advantages

Special price list for organisations

We offer a significant discount for trade organisations and manufacturing companies

Advantages

Worldwide shipping on request

We take care of all logistics and customs clearance. Fast delivery to Baltic countries

Advantages

After-sales service and support

Warranty service and repair, expert assistance in the operation of the instruments

Description of MACURCO CX-6-CO/CX-12-CO

Key features

  • CX-6, CX-6-CO, CX-6-NO2 – ETL LISTED: Conforms to Std. UL 2075, Certified to ULC Std. 588C 1
  • CX-12, CX-12-CO, CX-12-NO2 – Designed to meet UL Std. UL 2075 1
  • Low-level meter capable of displaying from 0-200 ppm of CO and/or 0-20 ppm of NO 2
  • The CX-xx meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO and/or NO2 exposure
  • Selectable fan and alarm relay activation
  • 5 A SPDT fan relay controls starters of exhaust fans
  • 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
  • 4-20 mA Current Loop
  • CX-xx mounts on a standard 4×4 electrical box and becomes cover for the box
  • Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
  • Calibration kit is available. One screw allows access for calibration or gas test

Applications

  • Parking garages
  • Mechanical rooms
  • Restaurants
  • Battery charging stations
  • Breweries
  • Storage facilities
  • Loading docks
  • Warehouses
  • Firehouses & ambulance bays
  • Refrigeration facilities
  • Vehicle repair facilities
  • Bus depots

Technical specifications of MACURCO CX-6-CO/CX-12-CO

Shipping Weight 1 pound (0 45 kg)
Size 4 1/2 x 4 x 2 1/8 in (11 4 X 11 4 X 5 3 cm)
Color White or Dark gray
Connections plugs/terminals
Mounting box (not included) 4×4 electric
Fan relay 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation for CO selectable at dIS (disable), 15, 25, 35 (default), 50 or 100 ppm
Fan relay actuation for NO2 selectable at dIS (disabled) 0 5, 0 7, 1 0, 1 2, 1 5, 1 7, 2 0, 2 2, 2 5 (default), 2 7, 3 0, 3 2, 3 5, 3 7, 4 0, 4 2, 4 5, 4 7, 5 0 ppm
Fan Delay Settings 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay 0 5A 120 V, 60 VA
Alarm relay actuation selectable N O (default) or N C
Alarm relay settings for CO dIS, 50, 100, 150, and 200 ppm (default)
Alarm relay settings for NO2 dIS, 1, 2, 3, 4, 5 (default), 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20 ppm
Current Loop 4-20 mA selectable to ‘bAS’ (default), ‘EnH’, OFF
Calibration Period Settings dis(default), 3, 6, 12 and 24 (months)
Buzzer 85 dBA at 10cm settable to On (default) or OFF
Digital display 4-digit LED selectable to On (default) or OFF
Operating Environment 0°F to 125° F (-18 o C to 52o C),10 to 90% RH non-condensing
6-Series Low Voltage
Power 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA standby
12-Series Line Voltage
Power 100-240VAC (50 TO 60 HZ)
Current 1 0 A MAX
Expand Table

How to buy MACURCO CX-6-CO/CX-12-CO

Model Number Gas Type Range (Units) Low Level Alarm Adjustable (Default) High Level Alarm Adjustable (Default) Expected Sensor Life Recommended Coverage Area
CX-6-CO | CX-12-CO Carbon Monoxide (CO) (CO) 0-200 PPM 0,15,25,35,50 or 100 PPM 0,50,100,150 or 200 PPM 4-5 Years** Up to 7,500 sq. ft.*
Expand Table

Accessories for MACURCO CX-6-CO/CX-12-CO

Photo Model Description
DVP-120, DVP-120M, DVP-120B, DVP-1200 Control Panels
PS-24, PS-24-H Step-down Transformers
DMK-1 Duct Mount Kit
HS-A, HS-B, HS-R, HS-C Horn and Strobe (4 color options)
MRS-485, BRS-485 Adapter Options
Calibration Kits Based on Gas Type
WHK-1 Weatherproof Housing Kit
Expand Table

User Guide and Instruction manual for MACURCO CX-6-CO/CX-12-CO

You can request the necessary certificates, documentation, instructions and user guide for MACURCO CX-6-CO/CX-12-CO using the special form.

You can buy MACURCO CX-6-CO/CX-12-CO in Latvia at a favourable price in «OLIL SIA» by leaving a request on the website, by phone +371 672 70580 or by email . MACURCO CX-6-CO/CX-12-CO price are subject to change depending on exchange rates. We deliver instruments by transport companies in Latvia, Estonia and Lithuania. Worldwide shipping to Europe, Asia, Africa, North and South America available on request.