DWYER DFS2 low limit freeze protection switch

The Series DFS2 Low Limit Freeze Protection Switch protects cooling coils in air handler systems by preventing frost build up. The thermostat and its capillary sensing element provide an antifreeze function by sensing the lowest temperature along any one foot section of capillary. The DPDT manual or automatic reset relays signal the building management system as well as cut off the fan. The Series DFS2 will detect temperature drops below the fixed safety value (set point) which can be set as low as 34°F (1°C) utilizing the visual set point indicator and set point screw.

			int(5223)
NULL
		

Made in USA. brand DWYER, model DFS2

Fast delivery to Latvia, Estonia and Lithuania. International delivery to Europe, Asia, Africa and other continents available on request
Our warehouse is located in Riga, Latvia.

Retailprice from $288,95

Available

Available

Founded in 1931, DWYER manufactures equipment for measurement, conversion and control – pressure, temperature, level, flow.

Advantages

Official distributor in Latvia

Time-tested American, European and Asian brands of control and measurent instruments

Advantages

Special price list for organisations

We offer a significant discount for trade organisations and manufacturing companies

Advantages

Worldwide shipping on request

We take care of all logistics and customs clearance. Fast delivery to Baltic countries

Advantages

After-sales service and support

Warranty service and repair, expert assistance in the operation of the instruments

Description of DWYER DFS2

PRODUCT APPLICATIONS

  • HVAC equipment
  • Heat exchangers and cooling coils

FEATURES

  • Vapor-filled copper capillary sensing element
  • Joint spring protector at capillary-bellow connection
  • Set point safety-lock protection and simple adjustment
  • Easy installation and wiring
  • Automatic and manual reset

Technical specifications of DWYER DFS2

  • Sensing Element: Vapor-filled capillary.
  • Operating Temperature: 14°F to 54°F (-10°C to 12°C).
  • Storage Temperature: 14°F to 158°F (-10°C to 70°C).
  • Capillary Overload Temperature: 392°F (200°C), maximum 60 minutes.
  • Humidity Limit: 0 to 95% RH, non-condensing.
  • Enclosure: Galvanized steel base, ABS cover.
  • Enclosure Rating: NEMA 1 (IP40).
  • Capillary Material: Copper.
  • Cable Entry: (1) M20 compression fitting.
  • Reset Action: Available in automatic or manual reset options.
  • Low-level Setpoint: Factory Set: 39°F (4°C), and safety lock secured; Adjustment via screwdriver slot.
  • Wire Connection: Terminal with wire-retaining screws.
  • Wire Size: Max. 14 AWG.
  • Electrical Rating: 24 to 250 VAC, 15 (8) A.
  • Electrical Connections: Two each NO/NC/Common.
  • Deadband: 1.8°F (fixed).
  • Weight: 1.6 lb (0.7 kg).
  • Compliance: CE.

How to buy DWYER DFS2

Model Description Price
DFS2-DA10 Low limit temperature control, 10 ft capillary with automatic reset
$288.95
DFS2-DA20 Low limit temperature control, 20 ft capillary with automatic reset
$378.75
DFS2-DM10 Low limit temperature control, 10 ft capillary with manual reset
$302.70
DFS2-DM20 Low limit temperature control, 20 ft capillary with manual reset
$387.00
Load More Items

Accessories for DWYER DFS2

Model Description Price
A-DFS2-C Capillary mounting clips (6 pcs)
$17.00
Load More Items

User Guide and Instruction manual for DWYER DFS2

You can request the necessary certificates, documentation, instructions and user guide for DWYER DFS2 using the special form.

You can buy DWYER DFS2 in Latvia at a price starting from288,95 $ in «OLIL SIA» by leaving a request on the website, by phone +371 672 70580 or by email . DWYER DFS2 price are subject to change depending on exchange rates. We deliver instruments by transport companies in Latvia, Estonia and Lithuania. Worldwide shipping to Europe, Asia, Africa, North and South America available on request.